What is a Mold Assessment?

I once again raise this question because I’ve been called in to provide yet another second opinion of a mold inspection that consisted of nothing more than the collection of a few air samples for mold spores.  I assure you that a correct mold assessment in accordance with the only industry standard of practice does not involve the random sampling of mold.  The only industry standard of practice is the ASTM D-7338 Assessment of Fungal Growth in Buildings.


The question of just what is a mold assessment is a frustrating and surprisingly hard question for many industry professionals to answer.  That’s right; many mold professionals just don’t know their own industry well enough to know the prevailing standard of practice.  When I’m asked to provide a second opinion on a mold inspection, I always want to talk with the original mold assessors.  Given the chance, I will always take the opportunity to try to raise the awareness of the original mold assessor and inform them of the ASTM D-7338 and the process of providing a valuable mold assessment and report.  I feel that this is best for our industry and for the consumer.


So just what is it that many mold assessors believe is a mold inspection?  Many believe that a mold assessment is simply testing for mold.  There is plenty of guidance on the value of mold sampling but if the ill-informed mold assessor isn’t aware of the industry standard of practice, the ASTM D-7338, there is little chance that they will be aware of the very public opinion of mold sampling.


Let’s just review the industry position on mold sampling.  Ten years ago, the ACGIH concluded that air testing provided a "snap shot" of conditions at the exact time and place of the sampling, but nothing more.   The Center for Disease Control, CDC's current position is that air sampling for mold is nothing more than a snap shot and that such a snap shot is not reliable, representative or worth the cost. The CDC states very clearly that “Any claim based solely on air sampling results is inherently suspect.”  The CDC goes on to state that “There is no reason to respond to questionable testing by conducting more of it.  I believe that is a very clear position from a reputable source. 


What does the laboratory say about the interpretation of the collected mold samples?

  • The client is solely responsible for the use and interpretation
  • Note: Interpretation is left to the company and/or persons who conducted the field work.
  • The “Lab” shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results.

 

The mold assessor that collected the mold samples is the laboratory’s client not the property owner.  That is something that the mold sampler seems to not understand.


Let’s look a bit further. When the following governmental and industry organizations were asked if mold testing is necessary, this is what they had to say.

  • American Industrial Hygiene Association, AIHA There are no standards for “acceptable” levels of mold in the indoor environment. If you know you have a mold problem, it is more important to spend time and resources solving the moisture problem and getting rid of the mold than to spend it on sampling. 
  • US Environmental Protection Agency, EPA If you know you have a mold problem, it is more important to spend time and resources solving the moisture problem and getting rid of the mold than to spend it on sampling. If visible mold growth is present, sampling is unnecessary.  Since no EPA or other federal limits have been set for mold or mold spores, sampling cannot be used to check a building's compliance with federal mold standards.
  • Occupational Health and Safety Administration, OSHA In most cases, if visible mold growth is present, sampling is unnecessary. Your first step should be to inspect for any evidence of water damage and visible mold growth.
  • U.S. Department of Labor There are no standards for acceptable levels of mold in buildings, and the lack of a definitive correlation between exposure levels and health effects makes interpreting the data difficult, if not impossible.
  • Center for Disease Control, CDC There are no accepted standards for mold sampling in indoor environments or for analyzing and interpreting the data in terms of human health.  Molds are ubiquitous in the environment, and can be found almost anywhere samples are taken.  It is not known, however, what quantity of mold is acceptable in indoor environments with respect to health.  CDC does not recommend routine sampling for molds. Generally, it is not necessary to identify the species of mold growing in a building.  Measurements of mold in air are not reliable or representative.  If mold is seen or smelled, there is a potential health risk; therefore, no matter what type of mold is present, you should arrange for its removal.
  • The Florida Department of Health, The Florida Department of Health does not recommend mold testing or sampling to see if you have a mold problem, or to see what kind of mold might be growing.
  • NYC Guidelines on Assessment and Remediation of Fungi in Indoor Environments, The Department of Health, DOH, should continue to emphasize in its public education materials that sampling for airborne mold is unlikely to provide reliable information for decision-making in damp or moldy buildings.

 

So, should you sample for mold? No, never for the purpose of mold investigation.  Why? There are too many variables impacting the results and the sample size is too small for air testing for mold to be reliable.  The type of mold will not change the necessary mold remediation.  The genus of mold is just not relevant or necessary unless you are trying to frighten a client into believing that they have “Toxic” mold.  Mold spore trap air samples do not have the ability to establish the presence of any mycotoxins.  Air sampling's lack of utility in determining the level of mold found in indoor air may be a surprise to some, given the frequent references to these tests and mold litigation.  


Unfortunately, those that reference mold testing in mold litigation are never directly involved in mold litigation or they would know what the reality is, mold sampling to the genus level is worthless in court.


Mold assessors should bear in mind that samples provide information about a site as it existed at the time tested.  However, the findings may not represent conditions at a time in the past or future, even the relatively recent past or near future. Changes in the kinds, concentrations, and proportions of biological agents in the air can be rapid and substantial.  Bioaerosols: Assessment and Control, Section 2.4.2.2.


ASTM D7338 Standard Guide for Assessment of Fungal Growth in Buildings 7.1 The most important requirement of an assessment for fungal growth is an on-site inspection of the subject building. It is very important to remember that the ASTM D-7338 is the only recognized standard for mold assessment.  According to the ASTM D-7338 the parts of a mold assessment include:

  • the collection of background information,
  • the formulation of a hypothesis or hypotheses,
  • on-site inspection including moisture dynamics,
  • an evaluation of the HVAC system,
  • hypothesis testing,
  • site documentation and written report.

 

The scope of work defines the problem and, just as importantly, which part of the basic assessment and which of the procedures are to be performed.   The scope of work will define the inspection boundaries.  The ASTM D-7338 clearly states that “Within the inspection boundary, all surfaces should be inspected to the extent feasible, including

  • above suspended ceilings and
  • inside pipe chases,
  • attics, and
  • crawlspaces.

The exterior of the building and adjacent grounds should also be inspected for moisture intrusion sites and air leaks.”


The mold inspector that only samples for mold and provides nothing more than a laboratory report will attempt to exclude virtually all areas of a building from his responsibility.  Below is an excerpt from a peer reviewed mold inspection report “Disclaimer”.  It is a remarkable example of how some mold inspectors attempt to alleviate themselves form the responsibility of the very job that they were hired to perform.

DISCLAIMER

"Certain areas are considered inaccessible and impractical to inspect including, but not limited to,

the interiors of walls and inaccessible areas below; areas beneath wood floors over concrete; areas concealed by floor coverings; and areas to which there is no access without defacing or tearing out lumber, masonry, roofing or finished workmanship; structures; portions of the attic concealed or made inaccessible by insulation, belongings, equipment or ducting; portions of the attic or roof cavity concealed due to inadequate crawl space; areas of the attic or crawl space made inaccessible due to construction; interiors of enclosed boxed eaves; portions of the sub area concealed or made inaccessible by ducting or insulation; enclosed bay windows; portions of the interior made inaccessible by furnishings; areas where locks prevented access; areas concealed by appliances; areas concealed by stored materials; and areas concealed by heavy vegetation.

There is no economically practical method to make these areas accessible. However, they may be subject to attack by microbial organisms. No opinion is rendered concerning the conditions in these aforementioned or other inaccessible areas. Furthermore, mold grows. As such, the inspection and report produced by Mold Assessor is not a guarantee that mold does not exist.

As a courtesy Mold Assessor may point out conditions that contribute to mold growth but such comments are not part of the bargained for report, protocol, or supplemental information. The protocol is not intended to be either exhaustive or inclusive of all pertinent requirements, methods or procedures that might be appropriate on a particular mold remediation project.

Anyone using this document should understand the limitations with its use, and rely on his or her own independent judgment, or as appropriate, seek the advice of competent professionals in determining the exercise of reasonable care in any given situation."


This type of disclaimer is an example of how some mold inspectors are intent on limiting their area of responsibility.  What exactly are property owners that hire this mold inspector paying for?  What exactly is the value provided by the mold assessor?  Most importantly, why the need to limit the area of responsibility in direct contradiction to the ASTM D-7338?  The answer is that this mold assessor, like many, had no idea that the ASTM D-7338 even existed. This mold assessor, like many, felt that the simple collection of air samples for mold was a mold inspection in direct contradiction to the government and industry positions sited above.


As with any industry the mold industry has a standard of practice that must be followed to provide a property owner with necessary and relevant information regarding any possible mold issue within their property.  Mold sampling will never have the ability to provide any of that necessary and relevant information


A mold inspection in accordance with the ASTM D-7338 will provide the property owner with a wealth of necessary and relevant information.


The ASTM D-7338 states in Section 7.5.3 Identification of Current Water Damage and Suspect Fungal Growth

All surfaces within the inspection boundary should be systematically evaluated for indicators of moisture damage and fungal growth.

Exposed surfaces (including building materials, furnishings, and contents) should be examined for past and ongoing damage including:

(1)  suspect fungal growth,

(2)  standing water

(3)  water stains,

(4)  dampness to touch, and

(5)  blistering, warping, de-lamination, or other deterioration.


The ASTM D-7338 states in Section 7.5.4 Identification of Potentials for Fungal Growth

The inspection should identify moisture sources and moisture pathways, including:

(1)  sites where condensation may occur,

(2)  equipment or activities which may release water,

(3)  pathways for water movement and

(4)  areas where leakage is likely.

   -  Staining patterns are often useful in identifying moisture sources.


The ASTM D-7338 states in Section 7.5.5 Presence of Odors

Detection of musty odors should always be noted.

(1)  Sources of such odors should be located.

(2)  If the source is not apparent, intrusive investigation may be required.


The ASTM D-7338 states in Section 7.5.6 Classification of Inspection Observations

Classify each distinct area or area of interest within the inspection boundary as one of the following categories:

(1)  no apparent fungal growth and no apparent water damage;

(2)  water damage having no visually suspect or confirmed fungal growth,

(3)  visually suspect or confirmed fungal growth having no apparent water damage, &

(4)  water damage having visually suspect or confirmed fungal growth.


The ASTM D-7338 states in Section 7.5.8 HVAC Inspection, if applicable per the scope of work

The interiors of HVAC equipment in contact with ventilation air should be inspected for indicators of excessive moisture or suspect fungal growth.

Such areas may include intake and return plenums, filters, coils, condensate pans, fans, housing insulation, and supply ducts immediately downstream from the coils.


The ASTM D-7338 states in Section 7.6.1 Site Map—A site/floor plan should be prepared showing each inspection classification, as determined in 7.5.6.

The plan should be sufficiently detailed to allow each area of interest to the assessment to be unambiguously located.


The ASTM D-7338 states in Section 7.6.2 Documentation of Suspect Fungal Growth—Wherever suspect or confirmed fungal growth is identified during the inspection, documentation should include:

(1)  extent (for example, approximate square footage of suspect growth),

(2) severity (for example, relative darkness or continuity of stain), growth pattern (for example, light versus heavy growth and spotty versus continuous growth), and

(3)  clues to apparent cause (for example, exterior wall, condensation near a HVAC vent, associated with water staining).


The ASTM D-7338 states in Section 7.6.3 Documentation of Moisture Damage—In addition to documenting the location of moisture damage, as above, further documentation should include:

(1)  apparent sources of leaks and other moisture sources, and

(2)  apparent timing and duration (for example, whether the moisture has been resolved, active (currently wet) or the moisture source is likely to reoccur


The ASTM D-7338 states in Section 7.6.4 Visual Documentation—Photographs or videotapes are often helpful in documenting building conditions. Captions should note location, timing, and context.


The ASTM D-7338 states in Section 7.6.5 Additional Detail—Start and stop time, temperature, humidity, occupancy, condition, and housekeeping of the property.


With a clearly written standard of practice for mold assessment, it’s truly hard to believe that there are so many mold assessors that provide a client little more than a few air samples for mold and call it a mold inspection.  Worse yet is when these mold inspectors call the simple collection of air samples for mold air quality samples.  Both are perfect examples of over selling and under delivering.


More importantly, I would stress that a mold assessment is NOT the collection of mold samples or testing for mold.  It may include the collection of mold samples but the collection of mold samples is NOT, on its own, a mold assessment.


If you hire a licensed mold assessor you should receive a written report in accordance with the ASTM D-7338 signed by the licensed mold assessor that performed the assessment.  Not by someone in another location that never visited your home or office.  When you hire a licensed mold assessor you should receive the written report signed by the licensed mold assessor that performed the assessment and never be required to pay an additional fee for a written report.   


That’s ridicules, what are you paying for if you aren’t receiving a written mold assessment report from your licensed assessor.


So what should the written mold assessment report include?


As the ASTM D-7338 clearly states.  A detailed evaluation of data obtained from a building history and inspection to formulate an initial hypothesis about the

  • origin,
  • identity, location,
  • and extent of amplification of mold growth

 

The written report can then be provided to licensed mold remediators that can then provide you with a written estimate for the remediation.


Finally, I close with questions you should ask your mold assessor before you hire them.

 

 

 

 

John P. Lapotaire, CIEC

Certified Indoor Environmental Consultant

Indoor Air Quality Solutions, IAQS

Microshield Environmental Services, LLC

 




Add a Comment

(Enter the numbers shown in the above image)


Follow jlapotaire on Twitter


Review microshield-es.com on alexa.com
   

[Valid RSS]
Add this Content to Your Site
   


Latest Top (12) News


EPISODE497 - Radio Joe and the Z-man – Using Building Science & EPA’s Moisture Control Guide to Improve Indoor Air!
Today Radio Joe and the Z-man will be discussing how to solve indoor environmental quality problems by using building science fundamentals and the “EPA Moisture Control Guide”. To get at the root of IEQ problems you must understand buildings and building science. Today we will discuss some great information from people like Joe Lstiburek, Terry Brennan, Bill Rose, Mike McGuinness and Lew Harriman. We start with an overview of building science concepts that will help you solve problems. Our foundation will be the 4 P’s (people, pollutant, pathway, pressurization). From there we will go into how to use the wealth of information in the EPA “Moisture Control Guide” and then go through some case studies. On a future show we will get into how to include the information in your reports

Thu, 11 Oct 2018 11:00:00 -0500


EPISODE509: Nick Hurst – US EPA, Indoor Environments Division – The EPA Indoor airPLUS Program
This week on IAQradio+ we welcome Nick Hurst. Nick is an Environmental Protection Specialist with the US EPA and the Program Manager of EPA’s Indoor airPLUS label for new homes. He has been involved in the construction industry for over 17 years as a self-employed remodeling contractor, project manager, green building consultant, and trainer. Nick earned a Master’s in Technology concentrating in Building Science from Appalachian State University in Boone, NC, and he later served as Education and Outreach Director for the North Carolina Energy Efficiency Alliance at ASU’s Energy Center. Before coming to EPA, Nick also worked as a consultant at ICF in their Federal Energy Efficiency portfolio. Nick is also a BPI Building Analyst and participates with a number of standard setting organizations and technical committees in the building industry.

Fri, 29 Jun 2018 15:30:00 -0500


EPISODE508: HOMEChem Open House – House Observations of Microbial and Environmental Chemistry
This week on IAQradio+ will be broadcasting live from the Open House event for the HOMEChem study at the University of Texas Austin’s, J.J. Pickle Research Campus. The HOMEChem experiment (House Observations of Microbial and Environmental Chemistry) incorporates state-of-the-art measurements performed by over 20 investigators and their teams from the fields of chemistry, microbiology, and engineering. This experiment engages far more institutions and disciplines than ever applied to the study of a home. This research study is sponsored by the Alfred P. Sloan Foundation Chemistry of Indoor Environments Program and it will take place this summer at the University of Texas at Austin’s UTest House. Our guests for this special show are Marina Vance (HOMEChem Co-PIs / organizer) Delphine Farmer (HOMEChem Co-PIs / organizer) Atila Novoselac (HOMEChem host, specialist on the UTest house) Rich Corsi (HOMEChem host, indoor air specialist) Dr. Richard L. Corsi is the Joe J. King Chair in Engineering #2 in the Department of Civil, Architectural and Environmental Engineering (CAEE) at The University of Texas at Austin (UT Austin). He has served on the faculty of CAEE at UT Austin for nearly 25 years, after starting his career in the School of Engineering at the University of Guelph in Ontario, Canada. Dr. Corsi is highly regarded as an educator. He has received numerous teaching awards, and in 2015 was inducted into the Academy of Distinguished Teachers, an honor held for the top 5% of teachers across UT Austin. He also received a Regents’ Outstanding Teaching Award for the entire UT system in 2016. Dr. Corsi’s research focuses on sources, physics and chemistry of indoor air pollution, particularly as related to pollutant interactions with indoor materials and innovative strategies for using such interactions to reduce human exposure to air pollution of both outdoor and indoor origin. He has served as principal investigator on over 70 projects, as major advisor to over 50 undergraduate and 70 graduate students, and as co-author on over 300 journal/conference papers, reports, and book chapters. His work has been featured in National Geographic, The Economist, Business Week, National Wildlife, Prevention, Men’s Health, National Public Radio’s Science Friday, Science Studio, the Academic Minute, the Canadian television series The Nature of Things, and more. Delphine Farmer, PhD Dr. Delphine Farmer is an Associate Professor in the Department of Chemistry at Colorado State

Fri, 22 Jun 2018 15:30:00 -0500


EPISODE508: HOMEChem Open House – House Observations of Microbial and Environmental Chemistry
This week on IAQradio+ will be broadcasting live from the Open House event for the HOMEChem study at the University of Texas Austin’s, J.J. Pickle Research Campus. The HOMEChem experiment (House Observations of Microbial and Environmental Chemistry) incorporates state-of-the-art measurements performed by over 20 investigators and their teams from the fields of chemistry, microbiology, and engineering. This experiment engages far more institutions and disciplines than ever applied to the study of a home. This research study is sponsored by the Alfred P. Sloan Foundation Chemistry of Indoor Environments Program and it will take place this summer at the University of Texas at Austin’s UTest House. Our guests for this special show are Marina Vance (HOMEChem Co-PIs / organizer) Delphine Farmer (HOMEChem Co-PIs / organizer) Atila Novoselac (HOMEChem host, specialist on the UTest house) Rich Corsi (HOMEChem host, indoor air specialist) Dr. Richard L. Corsi is the Joe J. King Chair in Engineering #2 in the Department of Civil, Architectural and Environmental Engineering (CAEE) at The University of Texas at Austin (UT Austin). He has served on the faculty of CAEE at UT Austin for nearly 25 years, after starting his career in the School of Engineering at the University of Guelph in Ontario, Canada. Dr. Corsi is highly regarded as an educator. He has received numerous teaching awards, and in 2015 was inducted into the Academy of Distinguished Teachers, an honor held for the top 5% of teachers across UT Austin. He also received a Regents’ Outstanding Teaching Award for the entire UT system in 2016. Dr. Corsi’s research focuses on sources, physics and chemistry of indoor air pollution, particularly as related to pollutant interactions with indoor materials and innovative strategies for using such interactions to reduce human exposure to air pollution of both outdoor and indoor origin. He has served as principal investigator on over 70 projects, as major advisor to over 50 undergraduate and 70 graduate students, and as co-author on over 300 journal/conference papers, reports, and book chapters. His work has been featured in National Geographic, The Economist, Business Week, National Wildlife, Prevention, Men’s Health, National Public Radio’s Science Friday, Science Studio, the Academic Minute, the Canadian television series The Nature of Things, and more. Delphine Farmer, PhD Dr. Delphine Farmer is an Associate Professor in the Department of Chemistry at Colorado State

Fri, 22 Jun 2018 15:30:00 -0500


EPISODE508: HOMEChem Open House – House Observations of Microbial and Environmental Chemistry
This week on IAQradio+ will be broadcasting live from the Open House event for the HOMEChem study at the University of Texas Austin’s, J.J. Pickle Research Campus. The HOMEChem experiment (House Observations of Microbial and Environmental Chemistry) incorporates state-of-the-art measurements performed by over 20 investigators and their teams from the fields of chemistry, microbiology, and engineering. This experiment engages far more institutions and disciplines than ever applied to the study of a home. This research study is sponsored by the Alfred P. Sloan Foundation Chemistry of Indoor Environments Program and it will take place this summer at the University of Texas at Austin’s UTest House. Our guests for this special show are Marina Vance (HOMEChem Co-PIs / organizer) Delphine Farmer (HOMEChem Co-PIs / organizer) Atila Novoselac (HOMEChem host, specialist on the UTest house) Rich Corsi (HOMEChem host, indoor air specialist) Dr. Richard L. Corsi is the Joe J. King Chair in Engineering #2 in the Department of Civil, Architectural and Environmental Engineering (CAEE) at The University of Texas at Austin (UT Austin). He has served on the faculty of CAEE at UT Austin for nearly 25 years, after starting his career in the School of Engineering at the University of Guelph in Ontario, Canada. Dr. Corsi is highly regarded as an educator. He has received numerous teaching awards, and in 2015 was inducted into the Academy of Distinguished Teachers, an honor held for the top 5% of teachers across UT Austin. He also received a Regents’ Outstanding Teaching Award for the entire UT system in 2016. Dr. Corsi’s research focuses on sources, physics and chemistry of indoor air pollution, particularly as related to pollutant interactions with indoor materials and innovative strategies for using such interactions to reduce human exposure to air pollution of both outdoor and indoor origin. He has served as principal investigator on over 70 projects, as major advisor to over 50 undergraduate and 70 graduate students, and as co-author on over 300 journal/conference papers, reports, and book chapters. His work has been featured in National Geographic, The Economist, Business Week, National Wildlife, Prevention, Men’s Health, National Public Radio’s Science Friday, Science Studio, the Academic Minute, the Canadian television series The Nature of Things, and more. Delphine Farmer, PhD Dr. Delphine Farmer is an Associate Professor in the Department of Chemistry at Colorado State

Fri, 22 Jun 2018 15:30:00 -0500


EPISODE507: Radio Joe & Bob Krell Report LIVE – IAQA Mid Atlantic Conference – Eva King, PhD & Wei Tang, PhD
This week on IAQradio+ and Healthy Indoors Magazine are coordinating on a live show from the IAQA Mid Atlantic Conference in Princeton, New Jersey. Today’s guests include Eva King, PhD and Wei Tang, PhD. Dr. Eva King, CIEC is the Principal Scientist and Founder of AURA EnviroScience. Eva received her Masters degree in Biochemistry from the University of Bielefeld, Germany, and her Doctorate from the University of Oxford, UK. Dr. Wei Tang is the founder, President and Laboratory Director of QLab in Metuchen, New Jersey. Dr. Eva King, CIEC is the Principal Scientist and Founder of AURA EnviroScience. Eva received her Masters degree in Biochemistry from the University of Bielefeld, Germany, and her Doctorate from the University of Oxford, UK. She has been involved in investigations and research into indoor environments and health, allergens, asthma and immunology for over 10 years, and has developed a wide range of new methods for exposure assessment. She has helped clients in different industry sectors, accelerating product development and validation, and assisted in clinical trials and other research studies. Her work has been published in many peer-reviewed scientific publications. Eva is an active member of the indoor air quality, industrial hygiene, and allergy research communities, and served on the Board of Directors of IAQA, and as Convention Committee Chair between 2013 and 2017. Dr. Wei Tang is the founder, President and Laboratory Director of QLab in Metuchen, New Jersey. Dr. Tang graduated from Cornell University with his Master and Ph.D. degrees in Soil Microbiology. He has conducted numerous research projects in Cornell University Soil Microbiology Laboratory in using microorganisms for bioremediation of environmental organic pollutants. His work in recent years has been focused on microbiological sampling and analysis methods for indoor environmental quality assessment. He has taught professional development courses and presented frequently at national conferences on analysis of indoor microorganisms and also on various topics including investigation and remediation of microbial growth in indoor environment. Dr. Tang is the inventor of several advanced microbial sampling devices including AccuScience Triple Gel-Tape, Sweep-Swab and Sponge-Swab. He also developed several advanced analytical methods such as AccuScience High Performance Spore Count and AccuScience Triplicate Analysis. Dr. Tang served on IAQA Board of Directors for three terms. H

Fri, 15 Jun 2018 15:15:00 -0500


EPISODE507: Radio Joe & Bob Krell Report LIVE – IAQA Mid Atlantic Conference – Eva King, PhD & Wei Tang, PhD
This week on IAQradio+ and Healthy Indoors Magazine are coordinating on a live show from the IAQA Mid Atlantic Conference in Princeton, New Jersey. Today’s guests include Eva King, PhD and Wei Tang, PhD. Dr. Eva King, CIEC is the Principal Scientist and Founder of AURA EnviroScience. Eva received her Masters degree in Biochemistry from the University of Bielefeld, Germany, and her Doctorate from the University of Oxford, UK. Dr. Wei Tang is the founder, President and Laboratory Director of QLab in Metuchen, New Jersey. Dr. Eva King, CIEC is the Principal Scientist and Founder of AURA EnviroScience. Eva received her Masters degree in Biochemistry from the University of Bielefeld, Germany, and her Doctorate from the University of Oxford, UK. She has been involved in investigations and research into indoor environments and health, allergens, asthma and immunology for over 10 years, and has developed a wide range of new methods for exposure assessment. She has helped clients in different industry sectors, accelerating product development and validation, and assisted in clinical trials and other research studies. Her work has been published in many peer-reviewed scientific publications. Eva is an active member of the indoor air quality, industrial hygiene, and allergy research communities, and served on the Board of Directors of IAQA, and as Convention Committee Chair between 2013 and 2017. Dr. Wei Tang is the founder, President and Laboratory Director of QLab in Metuchen, New Jersey. Dr. Tang graduated from Cornell University with his Master and Ph.D. degrees in Soil Microbiology. He has conducted numerous research projects in Cornell University Soil Microbiology Laboratory in using microorganisms for bioremediation of environmental organic pollutants. His work in recent years has been focused on microbiological sampling and analysis methods for indoor environmental quality assessment. He has taught professional development courses and presented frequently at national conferences on analysis of indoor microorganisms and also on various topics including investigation and remediation of microbial growth in indoor environment. Dr. Tang is the inventor of several advanced microbial sampling devices including AccuScience Triple Gel-Tape, Sweep-Swab and Sponge-Swab. He also developed several advanced analytical methods such as AccuScience High Performance Spore Count and AccuScience Triplicate Analysis. Dr. Tang served on IAQA Board of Directors for three terms. H

Fri, 15 Jun 2018 15:15:00 -0500


EPISODE505 - Ed Cross – “The Restoration Lawyer” – Restoration Industry Legal Issues & Answers
This week on IAQradio+ we welcome “The Restoration Lawyer” Ed Cross to discuss current legal issues and answers for restoration professionals. Mr. Cross has built a successful law practice that specially caters to the needs of insurance damage repair contractors and remediators. Mr. Cross received a Bachelor’s Degree in Speech Communications with an emphasis on Public Speaking from California State University at Northridge in 1986 (Dean’s Honor Roll), and his Juris Doctor Degree from Western State University in Fullerton California. Ed is also well known for his risk management advice, cleaning and restoration contracts and related forms available for free and/or for purchase on his website edcross.com . These are simple one page forms in plain English that protect payment rights and deter lawsuits. He has recently added contract forms specific to the needs of those doing work in Texas and Florida.

Fri, 25 May 2018 15:15:00 -0500


EPISODE505 - Ed Cross – “The Restoration Lawyer” – Restoration Industry Legal Issues & Answers
This week on IAQradio+ we welcome “The Restoration Lawyer” Ed Cross to discuss current legal issues and answers for restoration professionals. Mr. Cross has built a successful law practice that specially caters to the needs of insurance damage repair contractors and remediators. Mr. Cross received a Bachelor’s Degree in Speech Communications with an emphasis on Public Speaking from California State University at Northridge in 1986 (Dean’s Honor Roll), and his Juris Doctor Degree from Western State University in Fullerton California. Ed is also well known for his risk management advice, cleaning and restoration contracts and related forms available for free and/or for purchase on his website edcross.com . These are simple one page forms in plain English that protect payment rights and deter lawsuits. He has recently added contract forms specific to the needs of those doing work in Texas and Florida.

Fri, 25 May 2018 15:15:00 -0500


EPISODE502: Tedd Benson – Bensonwood & Unity Homes Bridging the Gap! The Search for a Better Way to Build & Bob Krell – Healthy Indoors Magazine An Industry Update
This week on IAQ Radio+ we look forward to a great discussion on better ways to build and an industry update. Tedd Benson of Bensonwood and Unity Homes and Bob Krell of Healthy Indoors Magazine are our guests this week. Tedd Benson the founder of Bensonwood (1973) and Unity Homes (2012), has devoted his life to developing a better way to build. A key figure in the revival of timber framing in America, he was one of the founders of the Timber Framers Guild of North America (1984) and authored four books on the subject. Through the decades, Bensonwood established itself as a creative leader in timber frame design, engineering, craftsmanship, and CAD-CAM technology.

Fri, 27 Apr 2018 14:45:00 -0500


EPISODE502: Tedd Benson – Bensonwood & Unity Homes Bridging the Gap! The Search for a Better Way to Build & Bob Krell – Healthy Indoors Magazine An Industry Update
This week on IAQ Radio+ we look forward to a great discussion on better ways to build and an industry update. Tedd Benson of Bensonwood and Unity Homes and Bob Krell of Healthy Indoors Magazine are our guests this week. Tedd Benson the founder of Bensonwood (1973) and Unity Homes (2012), has devoted his life to developing a better way to build. A key figure in the revival of timber framing in America, he was one of the founders of the Timber Framers Guild of North America (1984) and authored four books on the subject. Through the decades, Bensonwood established itself as a creative leader in timber frame design, engineering, craftsmanship, and CAD-CAM technology.

Fri, 27 Apr 2018 14:45:00 -0500


EPISODE500: Radio Joe & The Z-man – Interviewed by John Lapotaire, Bob Krell, John Downey & Pete Consigli 10+ Years and 500 shows; What have We Learned?
This week on IAQradio+, Radio Joe & The Z-man are celebrating 10+ Years and 500 shows! It’s been an interesting journey from when podcasts were a new thing to where it seems everyone has a podcast. This week we turn the tables on the IAQ Radio co-hosts with questions from frequent listeners, guests and industry leaders. The four industry experts we have lined up come from unique perspectives and all have been guests and contributors. They have also listened to the show over our 10+ years and they have given freely of their time to help their respective portions of the indoor air quality and restoration industries. We look forward to answering their questions about IAQ Radio and what we have learned through 500 shows and 10+ years “on the air”.

Fri, 06 Apr 2018 14:30:00 -0500
Follow Microshields IAQ News and Headlines Bloglines RSS Feed

Subscribe with Bloglines

 



IAQ News and Articles

Latest Top (10) News
http://recordings.talkshoe.com/rss1547.xml